
BSC Building America Performance
Criteria
Requirements: Design
- Residences must reduce whole house energy use (HVAC, hot water,
lighting, and all appliances/plug loads) as stipulated in the table
below:
| Single Homes |
40% |
60-65 |
| Communities |
30% |
70-75 |
- Whole-house dilution ventilation: a mechanical ventilation system
must be installed to be capable of meeting ASHRAE Standard 62.2 which
stipfulates a ventilation rate of 7.5 CFM per person (counted as the
number of bedrooms plus one) plus 0.01 CFM per square foot of floor
area. While 62.2 stipulates that operation of the ventilation system
is at the occupant's discretion and the Standard is silent regarding
whole-house distribution of ventilation air, this Performance Criteria
stipulates that the 62.2 ventilation flow rate be delivered at least
one-third of the time and that whole-house distribution is required.
- Local exhaust ventilation: Intermittent spot exhaust of 100 CFM
must be provided for each kitchen (no recirculating cooktop hoods).
Intermittent spot exhaust of 50 CFM or continuous exhaust of 20 CFM
when the building is occupied must be provided for each room having
a toilet, bath, or shower.
- Ventilation intake locations: When a supply-only or balanced ventilation
system is used, the intake must go through an outside wall and not the
roof (due to proximity to exhaust/vent pollutants, and heated air/VOC's/odors
from the roof). Wall intakes should be located at least 10 feet from,
and not directly above, any wall exhaust or vent.
- All combustion appliances (except a gas stove or cooktop) in the
conditioned space must be sealed combustion. Specifically, any furnace
inside conditioned space must be a sealed-combustion 90%+ unit. Any
water heater inside conditioned space must be direct- power-vented.
Any boiler inside a conditioned space must be sealed combustion.
- Windows with the following climate-specific performance values must
be used:
| Zones 1-3 |
0.40
|
0.35
|
| Zones 4-8 |
0.35
|
0.40
|
- All ducts and air handling equipment must be in the conditioned
space.
- Major appliances (refrigerator, clothes washer, and dishwasher)
must achieve Energy Star performance in the top one-third of the DOE
Energy Guide rating scale.
- All lighting must be Energy Star qualified with the following exceptions:
motion-sensitive outdoor spotlights and solar-powered accent and pathway
lighting. LED technology is currently not certified by Energy Star,
however LEDs are acceptable.
- Carbon monoxide detectors (hard-wired units) must be installed (at
one per every approximate 1000 square feet) in any house containing
combustion appliances, and/or an attached garage.
Requirements: Testing
- Building America testing of the house must be completed as part
of the commissioning process. The SNAPSHOT form is a testing template
and is available for download to record the testing information (Snapshot
Form). Instructions for completing the form are also available
(Snapshot
Instructions).
- In a production setting, each model type (i.e., floor plan) must
be tested until two consecutive houses of this model type meet testing
requirements. Additional, testing on this model type can be reduced
to a sampling rate of 1 in 7 (i.e., 1 test, with 6 "referenced" houses).
Small additions to a floor plan (e.g., bay window, conversion of den
to bedroom) are considered to be the same model type; major changes
(e.g., bonus room over the garage, conversion of garage into a hobby
room, etc) must be considered a separate model type. Unique or custom
house plans must each be individually tested.
- Air leakage (determined by pressurization testing) must be less
than 2.5 square inches/100 square feet surface area leakage ratio (CGSB,
calculated at a 10 Pa pressure differential); or 1.25 square inches/100
square feet leakage ratio (ASTM, calculated at a 4 Pa pressure differential);
or 0.25 CFM/square foot of building enclosure surface area at a 50 Pascal
air pressure differential. The calculation of the building enclosure
area includes the foundation or below-grade surface areas. If
the house is divided into multiple conditioned zones, such as conditioned
attics or conditioned crawl space, the blower door requirement must
be met with the access to the space open, connecting the zones.
- Total space conditioning system duct leakage must be less than five
percent of the total air handling system rated air flow at high speed
(nominal 400 CFM per ton) determined by pressurization testing at 25
Pa. Two compliance mechanisms are acceptable: (1) test total duct leakage
at finish stage, or (2) test total duct leakage at duct rough-in stage.
When more than one air handler exists, each air handling system must
individually meet the requirement. If zoning is used, all zone dampers
must be open. Manual or motorized outside air ventilation dampers must
be closed.
- Local and whole-house mechanical ventilation system airflows must
be tested during commissioning of the building.
- Forced air systems that distribute air for heating must be designed
to provide balanced airflow to all conditioned spaces and zones (bedrooms,
hallways, basements). Inter-zonal air pressure differences, when doors
are closed, must be less than 3 Pa using passive transfer grilles or
jump ducts, or active return ducts (see
Transfer Grille Detail and
Transfer Grille Sizing Chart).
Recommendations: Mechanical
Equipment
- System external static pressure must be within manufacturer specifications
(0.5 WIC/125 Pa maximum typical).
Recommendations: Energy Conservation,
Occupant Comfort
- Information relating to the safe, healthy, comfortable operation
and maintenance of the building and systems that provide control over
space conditioning, hot water or lighting energy use should be provided
to occupants.
- The building enclosure and mechanical systems design should be capable
of maintaining comfortable conditions throughout the conditioned space
as defined by ASHRAE Standard 55-2004 (Thermal Environmental Conditions
for Human Occupancy).
- Indoor humidity should be maintained in the range of 25 to 60 percent
by controlled mechanical ventilation, mechanical cooling, or supplemental
dehumidification. In very cold, cold, and mixed climates (Zones 4 through
8) during the winter, indoor relative humidity should be kept on the
lower end of that range (see article "Relative
Humidity" for guidelines).
Recommendations: General Construction
- The building enclosure and sitework design and construction should
provide effective drainage measures to prevent moisture intrusion, conveying
water off of and away from the building.
- Design and construct the building foundation to prevent the entry
of moisture and other soil gases.
- Building assemblies should be designed and constructed to permit
drying of interstitial spaces.
- Design and construct building assemblies to prevent or control airflow
into insulation systems from both the interior and exterior.
- Use radon resistant construction practices as referenced in the
ASTM Standard "Radon Resistant Design and Construction of New Low Rise
Residential Buildings.
- Provide filtration systems for forced air systems that provide a
minimum MERV of 11 or higher.
Recommendations: Green Building
|